The influence of location of airborne particle source, ventilation rate, air inlet size, supply air velocity, air outlet location, and heat source on the distributions of airborne particle concentration and draught risk in an operating room is investigated. The investigation is carried out by using flow program with the k-e model of turbulence. Based on a standard case, five cases, each with one changed parameter, are computed, and the detailed field distributions of air velocity, temperature, airborne particle concentration, and draught risk are presented. The parametric study concludes that, for a better air quality and thermal comfort, it is desirable to use a higher inflow rate, a larger inlet area, and a uniform velocity profile of supply air. Outlet location and heat source have little influence on the distributions ofthe particle concentration in the room. It has also been found that the distributions of particle concentration in the recirculating zone are very sensitive to the location of the particle sources.